Scaffold system specifications

One row per scaffold system in the ScaFix catalogue: the bay lengths and depths it is planned with, the lift height the app erects it in, and the wall-tie rule the engine applies, with the document and page the rule comes from.

Generated from the catalogue the app plans with, so a new system or a changed rule shows here on the next build.

· How the numbers are computed ·

Layher Allround scaffolding around a house of 11.4 × 5.3 m with a gabled roof (eaves 4.5 m, ridge 6 m), drawn by the ScaFix 3D model
Layher Allround around the example house, as ScaFix draws it in 3D.

What are the bay lengths, depths and tie rules of each scaffold system?

ScaFix's catalogue holds 115 scaffold systems from 57 manufacturers. The most offered bay is 2.5 m (48 systems), the most offered depth 0.73 m (44), and 98 systems are erected in 2 m lifts. 91 of the 115 wall-tie rules cite a document and are checked against it; the other 24 show their spacings as «≈» estimates.

The catalogue at a glance

Ranges over every system and the values most systems share, counted from the table below.

MeasureRangeMost systemsSystems
Bay length0.7 m–3.07 m2.5 m48
Depth0.6 m–1.66 m0.73 m44
Main lift height1.52 m–2.13 m2 m98
Tie rows, vertical1.73 m–9 m4 m99
Source of the tie ruleSystemsShare
Manufacturer's document8977%
Regulation1210%
Third-party document65%
General rule (no document)87%

Every system: bays, depths, lift and wall-tie rule

115 rows, by maker. Bay lengths and depths are those of all the system's length variants; the tie rule is the one the engine applies to the system's main variant on an open (unclad) facade. «Estimate (≈)» marks a rule with no document, or one not yet checked against its document; Verification status by scaffold system gives each system's status and Wall tie spacing by system each rule's page references.

Download every row in English, with the tie pattern in separate columns and the page references: CSV or JSON.

SystemMakerTypeBay lengthsDepthsLiftTies: vertical / along the faceTie rule sourceStatus
Acrow QUICKSTAGE (AU)AcrowModular, wedge0.76 m · 1.27 m · 1.82 m · 2.43 m · 3.05 m0.76 m · 1.27 m1.98 m4 m / Every 3rd standard, staggered rowsWaco Kwikform «Kwikstage» guide PPM51 (08/2013) s. 5 (AS/NZS 1576.3 / 4576): up to 20 m ties at each end standard and at least every 3rd standard, vertically ≤ 4.0 m, staggeredDerived from the document
Acrow SUPERCUPLOK (AU)AcrowCuplock1.27 m · 1.83 m · 2.44 m · 3.05 m0.83 m · 1.27 m2 m4 m / Every standardAcrow «SUPERCUPLOK Technical Guide» (CUPLOK_OCT2026 issue J) s. 70–72 (PDF s. 71: ties commence where the height exceeds 3 × the least widthDerived from the document
AFIXFAST (Rosette spigot)AFIXFASTModular, rosette0.73 m · 1.04 m · 1.09 m · 1.4 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.22-1012 «AFIXFAST X52» (Afix Group NV, 04.12.2025) Anlage C §C.1 (PDF S. 63: 24 m), §C.5 (PDF S. 64: Schutzwand oberste Lage an jedem Ständer), Anlage D S.1 (PDF S. 67)Derived from the document
ALBERT BLITZFIX 70ALBERTFrame1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.1-885 ALBERT BLITZFIX 70 (12.07.2021, geänd. 23.08.2023, verl. 06.07.2026 bis 14.07.2031) Anlage B S. 5 §B.5 a–c (PDF S. 124: V-Halter nicht am Rand), Anlage C S. 1 (PDF S. 131: 1 V-Halter je 5 Felder), S. 13 (PDF S. 143: Schutzwand 2 V-Halter im 5-Felder-Bild, strengste Lesung 2 je angefangene 5 Felder)Derived from the document
ALBERT UNITAC 70ALBERTFrame1.5 m · 2 m · 2.5 m · 3 m0.74 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.1-979 ALBERT UNITAC 70 (02.04.2019, geänd. 19.03.2024 + 08.11.2024, bis 03.04.2029) Anlage B S. 3 §B.5 a–c (PDF S. 152), §B.10, Tab. B.5 (PDF S. 159: Netz 2 Dreieckhalter pro 5 Felder), Anlage C S. 1/2/3 (PDF S. 162–164: Dreieckhalter in jeder AnkerebeneDerived from the document
ALFIX ALBLITZ 70 SALFIXFrame0.73 m · 1.09 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m2 m4 m / Every standardDIBt Z-8.1-864 ALBLITZ 70 S (16.01.2023, bis 11.01.2028) Anlage B S. 3–5 §B.5 (PDF S. 382–384: Dreieckshalter nicht an den außenliegenden RahmenzügenDerived from the document
ALFIX FacadeALFIXFrame2 m · 2.5 m · 3 m0.73 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.1-862 ALFIX 70 (16.12.2020 bis 05.01.2027) Anl. B S. 7–8 §B.5 (PDF S. 179–180: V-Halter nicht an den Stirnseiten, Kopplungsrohre am Leitergang), Tab. B.4 (PDF S. 181), Anl. C S. 2 (PDF S. 185: 8 m versetzt, durchgehende Verankerung bei H = 4,0 m, mindestens 1 Dreieckshalter pro 5 Felder), S. 6 (PDF S. 189: Außenkonsole Dreieckshalter an jedem 2. Rahmenzug)Derived from the document
ALFIX ModulALFIXModular, rosette0.73 m · 1.09 m · 1.4 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m · 1.09 m · 1.4 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.22-906 ALFIX Modul (15.10.2021, Bescheide 31.01.2023, 02.04.2025, verl. 12.10.2026 bis 16.10.2031) Anl. C s.1–2 §C.1/§C.5 (PDF s. 196–197), Anl. D s.1 (PDF s. 201: mindestens 1 Dreieckshalter je 5 Felder, Schutzwandlage 2 je 5 Felder)Derived from the document
ALFIX UNIFIX 70ALFIXFrame1.5 m · 2 m · 2.5 m · 3 m0.74 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.1-847 UNIFIX 70 (21.12.2020, geänd. 04.04.2022, verl. bis 06.04.2027, geänd. 02.04.2025) Anlage B S. 8–9 §B.5 a–c (PDF S. 278–279: V-Halter nicht an den Stirnseiten), Anlage C S. 1 (PDF S. 284: mindestens 1 Dreieckshalter je 5 Felder, Schutzwandlage 2 je 5 Felder), S. 12 (Netz: 2 je 5 Felder) (2 pro 5 Felder als 2 je angefangene 5 Felder gelesen, strengste Lesung)Derived from the document
ALTEC AluSprintALTECFrame2.5 m · 3 m0.65 m2 m4 m / Every standardALTEC AluSprint AuV Regelausführung, Fassung 01.02.2010, §2.1 s.4 + §2.4.11 s.26 + Bild 17 s.24From the document
ALTRAD MAG 42ALTRADFrame3 m0.74 m2 m4 m / Every 2nd standard, staggered rowsALTRAD Saint Denis «Echafaudage MAG 42» fiche (ASD 11/2019Derived from the document
ALTRAD Baumann ProfiTech A 73 plusALTRAD BaumannFrame0.73 m · 1.09 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.1-910 (19.12.2019, Bescheid 06.01.2026, verl. bis 13.01.2027) PROFITECH A 73 PLUS Anlage B S. 1 §B.1 (PDF S. 120: 24 m), S. 2 §B.5 a–c, Anlage C S. 1/8 (PDF S. 127/134: oberste Lage jeder Ständer, ② Zusatzanker in 4 m vor teilweise offener Fassade, Leitergang in jeder Ankerebene)Derived from the document
ALTRAD Baumann ProfiTech S 73 plusALTRAD BaumannFrame0.73 m · 1.09 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.1-912 ProfiTech S 73 plus (08.05.2018, Bescheid 22.05.2023, verl. bis 03.06.2028) Anlage B S. 1 §B.1 (PDF S. 181: 24 m), S. 3 §B.5 (PDF S. 183), Anlage C S. 1 (PDF S. 191), S. 5/6/7/11 (Leitergang in jeder Ankerebene)Derived from the document
ALTRAD Baumann PROFITECH S 109ALTRAD BaumannFrame0.73 m · 1.09 m · 1.4 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m1.09 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.1-909 PROFITECH S 109 (18.05.2021, verl. 02.01.2025 bis 08.01.2030) Anlage B S. 3 §B.5 (PDF S. 148: V-Anker nicht an den außenliegenden RahmenzügenDerived from the document
MOSTOSTAL PlusAltrad MostostalFrame0.73 m · 1.09 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m · 1.09 m2 m2 m / Every 2nd standard, staggered rowsALTRAD-Mostostal «MOSTOSTAL Plus frame scaffolding — assembly manual» (EN, 05.2023) §3.5.1 p. 20 (PDF 22), §3.5.5 basic option p. 22 (PDF 24)Derived from the document
ROTAX Plus (Modular)Altrad MostostalModular, rosette0.73 m · 1.09 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m · 1.09 m2 m4 m / Every standardAltrad-Mostostal Instrukcja montażu ROTAX Plus 11.03.2026 §5 s. 32–34 (PDF 34–36) + RISE C900555 utg. 1 (2023-07-07, giltig t.o.m. 2033-07-07) vilkår 7–8Derived from the document
Aluhak (Facade)AluhakFrame0.72 m · 1 m · 1.2 m · 1.6 m · 1.9 m · 2.45 m · 3 m0.72 m2 m4 m / Every standardAluhak MONTERINGSVEILEDNING Rammestillas alu. kl. 1-3, M-02-2025-R001-NO rev. 25.06.2025 s.16–17Derived from the document
Aluhak (Modular)AluhakModular, rosette0.72 m · 1 m · 1.2 m · 1.6 m · 1.9 m · 2.45 m · 3 m0.72 m · 1 m · 1.2 m · 1.6 m2 m4 m / Every standardAluhak MONTERINGSVEILEDNING Systemstillas alu. kl. 1-6, M-01-2024-R001-NO rev. 18.12.2024 s.19–20Derived from the document
ANKA H-Tipi CepheANKAFrame2.5 m0.73 m2 m6 m / Every standardANKA «Cephe İskelesi Mamul ve Talimat El Kitabı» (30.12.2016) s. 29, 36–43 (ankraj detayları LC 3 / LC 4, 24 m), 44 (not published online)Derived from the document
assco FuturoasscoModular, rosette0.73 m · 1.09 m · 1.4 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m · 1.09 m · 1.4 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.22-841 ASSCO FUTURO (23.1.2024) Anl. C §C.1, §C.5Derived from the document
ASSCO QUADRO 70asscoFrame1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.1-190 ASSCO QUADRO 70 (27.04.2018, Bescheid 02.05.2023, verl. bis 02.05.2028) Anlage B S. 3 §B.5 a–c (PDF S. 183), Anlage C S. 1 (PDF S. 191), S. 5/6/11Derived from the document
AT-PAC RinglockAT-PACModular, rosette0.73 m · 1.09 m · 1.4 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m · 1.09 m · 1.4 m2 m4 m / Every 2nd standard, staggered rowsDoka Ringlock User Information 999817902 (09/2023) s.74 + Appendix D s.75–76 (= DIBt Z-8.22-992): 8 m versetzt, V-anchor ≥ 1 per 5 bays, wall tie directly below the node, lowest anchor plane b = 4 m with hSP ≤ 29 cm (s.76)Derived from the document
Bil-Jax Ring LockBil-JaxModular, rosette0.91 m · 1.22 m · 1.52 m · 1.83 m · 2.13 m · 2.44 m · 3.05 m0.73 m · 1.09 m · 1.4 m2 m≈4 m / Every 2nd standard, staggered rowsGeneral rule (no document)Estimate (≈): no manufacturer rule on file; follow the supplier's manual
BrandSafway SafLockBrandSafwayModular, rosette1.15 m · 1.57 m · 2.13 m · 3.05 m1.15 m · 1.57 m2 m6 m / ≤ 6 m apartBrandSafway «SafLock System Scaffold Technical Manual» ORN 2203 Rev. H (4/20) §3 p.57: first tie ≤ 3 × base width, ties at each end and ≤ 6 m along, ≤ 3 lifts vertically, the top within one lift, «all ties … as close to ledgers as possible» (not published online)From the document
Safway Systems Scaffold (USA)BrandSafwayModular, rosette1.83 m · 2.13 m · 2.44 m · 2.74 m · 3.05 m0.91 m · 1.22 m · 1.52 m2.13 m6.1 m / ≤ 6 m apartBrandSafway «Systems™ Scaffold Product Selection Guide» ORN 210 Rev. F § I.8b/8c (p.19): first tie ≤ 4 × base (3'-0": 3.66 m), ≤ 20 ft (≤ 3 ft wide) / 26 ft vertical, ends + ≤ 30 ft alongDerived from the document
Catari US RinglockCatariModular, rosette0.73 m · 1.04 m · 1.09 m · 1.4 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m · 1.09 m · 1.4 m2 m≈4 m / Every 2nd standard, staggered rowsGeneral rule (no document)Estimate (≈): no manufacturer rule on file; follow the supplier's manual
CETA MulticetaCETAModular, rosette0.77 m · 1.1 m · 1.5 m · 2 m · 2.5 m0.77 m · 1.1 m2 m4 m / Every 2nd standard, staggered rowsCETA «Manuale Ancoraggi» Rev.2 (10/2009) s. 3–4 «area d'influenza: massimo 22 m2 … non coperta da teli … 20 m»Derived from the document
Condor (Facade)CondorFrame1.8 m · 2.5 m1.05 m2 m≈4 m / Every 2nd standard, staggered rowsD.Lgs. 81/2008 art. 125 c. 6 «ancorato alla costruzione almeno in corrispondenza ad ogni due piani di ponteggio e ad ogni due montanti, con disposizione di ancoraggi a rombo o di pari efficacia»Estimate (≈): rule not yet checked against the manufacturer's document; follow the supplier's manual
Condor (Modular/Ringlock)CondorModular, rosette0.75 m · 1.05 m · 1.5 m · 2 m · 2.5 m · 3 m0.75 m · 1.05 m2 m4 m / Every 2nd standard, staggered rowsCondor MULTICOM, NF 096 certificate R25.03 (AFNOR, 01.12.2025, valid until 30.11.2026, no renewal published on 11.11.2026) annex s. 1/4 «Anchored in alternate rows all 24 m²»Derived from the document
Condor (Tube & coupler)CondorTube and coupler1 m · 1.2 m · 1.5 m · 2 m · 2.4 m0.73 m · 1.09 m · 1.4 m2 m≈4 m / Every 2nd standard, staggered rowsD.Lgs. 81/2008 art. 125 c. 6 «ancorato alla costruzione almeno in corrispondenza ad ogni due piani di ponteggio e ad ogni due montanti, con disposizione di ancoraggi a rombo o di pari efficacia»Estimate (≈): rule not yet checked against the manufacturer's document; follow the supplier's manual
DECKMAN (Facade)DECKMANFrame2 m · 2.5 m · 3 m0.73 m2 m≈4 m / Every 2nd standard, staggered rowsGeneral rule (no document)Estimate (≈): no manufacturer rule on file; follow the supplier's manual
DELTA (Facade)DELTAFrame0.73 m · 1.09 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m2 m4 m / Every 2nd standard, staggered rowsDELTA 73 DTR (Delta-Bud, Warszawa, wyd. 05.2020) §3.2.3 s. 57, §3.2.5 s. 58–59 «Podstawowe zasady wykonywania zakotwień» a–f, §6.2 s. 73, Wariant I s. 75 (not published online)From the document
DELTA (Modular/Wedge)DELTAModular, rosette0.73 m · 1.09 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m · 1.09 m2 m4 m / Every 2nd standard, staggered rowsDELTA MODUŁ Instrukcja montażu (Delta Rusztowania, Warszawa (not published online)From the document
Disk-lock Type B (China)Disk-lock (CN)Modular, rosette0.9 m · 1.2 m · 1.5 m · 1.8 m0.9 m · 1.2 m2 m4 m / Every 2nd standard, staggered rowsGB 55023-2022 §4.4.6 (≤ 3 跨 × 3 步 (not published online)Derived from the document
Doka RinglockDokaModular, rosette0.73 m · 1.09 m · 1.4 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m · 1.09 m · 1.4 m2 m4 m / Every 2nd standard, staggered rowsDoka Ringlock User Information 999817902 (09/2023) s.74 + Appendix D s.75–76 (= DIBt Z-8.22-992): 8 m versetzt, V-anchor ≥ 1 per 5 bays, wall tie directly below the node, lowest anchor plane b = 4 m with hSP ≤ 29 cm (s.76)Derived from the document
Excel Modular Scaffold (USA)ExcelCuplock1.22 m · 1.52 m · 1.83 m · 2.13 m · 2.44 m · 3.05 m0.61 m · 0.81 m · 1.07 m · 1.22 m2.04 m6.1 m / ≤ 6 m apartExcel Modular Scaffold «Standard Component Technical Manual» Rev. AL PDF p. 115 (printed p. 109, SIA Code of Safe Practices item 5): ties at each end and ≤ 30 ft along, ≤ 26 ft vertical, the top anchor no lower than 4 × the base dimension from the topDerived from the document
FERMAR Fer48FERMARFrame1 m · 1.5 m · 2 m · 2.5 m · 3 m0.7 m · 1.02 m2 m4 m / ≤ 6 m apartFERMAR «Andamio Europeo Fer48»: página web (leída 11.11.2026) § «Montaje» «La separación entre amarres será de 4 mtrs en altura y 6 en longitud» (primera fila ≤ 4 m: DERIVED)Derived from the document
Fortal (Facade)FortalFrame2 m · 2.5 m · 3 m0.65 m · 0.8 m2 m4 m / Every 2nd standardFortal NT-054 V12 (FORTEC 650, 01.2023) §8 s. 12 «Tous les 24 m² maximum … non recouvert … en évitant d'avoir plus de 2 niveaux ou deux travées entre deux points d'ancrages consécutifs» (figure: every 2nd frame line every 2 levels), «ancrages fixés à l'intersection des montants avec les traverses»Derived from the document
HAKI RamHAKIFrame1.66 m · 2.5 m · 3.05 m0.7 m2 m4 m / Every standardHAKI Monteringsveiledning Ram © HAKI AS 2023 06 (P000077) s. 26–27Derived from the document
HAKI UniversalHAKIModular, wedge2.5 m · 3.05 m0.7 m · 0.77 m · 1.01 m · 1.25 m · 1.66 m2 m4 m / Every standardHAKI Monteringsveiledning HAKI Universal (NO) © HAKI AS 2022 10 Rev 5 (P000073) s. 30Derived from the document
Hünnebeck BOSTA 70/100HünnebeckFrame2 m · 2.5 m · 3 m0.73 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.1-54.2 BOSTA 70 (16.06.2025, 07.05.2025 bis 07.05.2030) Anl. B §B.1 (PDF S. 176)/§B.5 (Ankerböcke nicht an den Stirnseiten, sonst einheitlich lange Gerüsthalter), Anl. C s.01/05/07Derived from the document
Hünnebeck MODEXHünnebeckModular, rosette0.74 m · 0.82 m · 1.13 m · 1.25 m · 1.5 m · 2 m · 2.5 m · 3 m0.82 m · 1.13 m2 m2 m / Every 2nd standard, staggered rowsHünnebeck MODEX User guide EN 2020 §9 Tab. 9.1, mønster 1/3 s. 113–117 (åpen fasadeDerived from the document
Instant Blitz-Fix 73InstantFrame0.73 m · 1.09 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m2 m4 m / Every standardRISE C901286 utg. 1 (2025-07-01) s. 3 pkt. 3 + s. 5 vilkår 5Derived from the document
JamaxJamaxFrame2 m · 3 m0.68 m2 m4 m / Every standardAlutec «Brukerveiledning JAMAX stillassystemer» 4. utg. rev. 2 (28.08.2025) § 6.4.1 s. 16 Fordelingsmåte 1 (distribution method 1) + «Enkelt fag» (single bay)Derived from the document
JUMBO FacadeJUMBOFrame2 m · 2.5 m · 3 m0.73 m2 m2 m / Every 2nd standard, staggered rowsJUMBO FLEX Montagevejledning JUMBO 2MM Facadestillads 3/2024 (DK) s. 6 §4.7.2 + figur 1 (forskudt ved hverandet knudepunkt), s. 2 (maks. byggehøjde 30 m)Derived from the document
JUMBO SystemJUMBOModular, rosette0.73 m · 1.04 m · 1.09 m · 1.4 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m · 1.09 m · 1.4 m2 m≈4 m / Every 2nd standard, staggered rowsGeneral rule (no document)Estimate (≈): no manufacturer rule on file; follow the supplier's manual
KERO RHU 070KEROFrame1.5 m · 2 m · 2.5 m · 3 m0.74 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.1-940 KERO RHU 070 (23.03.2023, bis 20.03.2028) Anlage B S. 3–4 §B.5 (PDF S. 216–217: jeder dritte Anker als Ankerbock, nicht an den Stirnseiten, sonst einheitlich lange Gerüsthalter), Anlage C S. 1/3/5 (PDF S. 223/225/227)Derived from the document
KERO RK 073KEROFrame1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.1-895 KERO RK 073 (06.02.2020, Bescheid 24.02.2025, bis 07.02.2030) Anlage B S. 4 §B.5 + Tab. B.2 (PDF S. 163), S. 7 (PDF S. 166), Anlage C S. 1 (PDF S. 173): «Gerüsthalter "lang"»Derived from the document
KERO RPL 070KEROFrame1.5 m · 2 m · 2.5 m · 3 m0.74 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.1-975 KERO RPL 070 (02.04.2019, verl. 19.03.2024 bis 03.04.2029) Anlage B S. 3 §B.5 a–c (PDF S. 138), §B.10, Tab. B.5 (PDF S. 145: Netz 2 Dreieckhalter pro 5 Felder), Anlage C S. 1/2/3 (PDF S. 148–150: L = 3,00 m in 4 m Höhe alle Knoten) (2 pro 5 Felder als 2 je angefangene 5 Felder gelesen, strengste Lesung)Derived from the document
Layher AllroundLayherModular, rosette2.57 m · 3.07 m0.73 m · 1.09 m · 1.4 m2 m4 m / Every standardDIBt Z-8.22-64 (23.04.2018, forlenget 02.05.2027) Anl. C s.2 §C.5 Ausf. B + Anl. D s.3Derived from the document
Layher Allround STAR 70LayherFrame0.73 m · 1.09 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.1-919 Layher Allround STAR 70 (07.11.2022, bis 02.11.2027) Anlage B S. 3 §B.5 (PDF S. 145: V-Anker nicht an den außenliegenden RahmenzügenDerived from the document
Layher BlitzLayherFrame1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m · 1.09 m2 m4 m / Every standardDIBt Z-8.1-16.2 Anlage B s. 1 §B.1 + s. 4 §B.5 bDerived from the document
Layher Blitz 70 AluLayherFrame0.73 m · 1.09 m · 2.07 m · 2.57 m · 3.07 m0.73 m2 m4 m / Every standardDIBt Z-8.1-844 Layher Blitz Gerüst 70 Alu (20.04.2020, verl. bis 21.04.2030) Anlage B §B.1 (PDF S. 178), §B.5 a–b (PDF S. 180), Anlage C S. 1 (PDF S. 188)Derived from the document
Metaltech Saferstack (USA)MetaltechFrame2.13 m · 2.44 m · 3.05 m0.91 m · 1.07 m · 1.52 m1.93 m4 m / ≤ 6 m apartMetaltech «Exterior Scaffolding Set Up Instructions / Safety Guidelines» (undated poster, PDF 22.04.2015) p. 1: 3 to 1 rule (tie above 3 × the smallest base dimension)Derived from the document
Metaltech Saferstack Mason (USA)MetaltechFrame2.13 m · 2.44 m · 3.05 m0.61 m · 0.76 m · 1.22 m · 1.52 m1.52 m4 m / ≤ 6 m apartMetaltech «Exterior Scaffolding Set Up Instructions / Safety Guidelines» (undated poster, PDF 22.04.2015) p. 1: 3 to 1 rule (24" narrowest frame: 1.83 m)Derived from the document
MJ COMBIMJModular, rosette0.73 m · 1.04 m · 1.09 m · 1.4 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m · 1.09 m · 1.4 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.22-921 MJ COMBI (13.10.2020, geänd. 05.09.2025, verl. bis 04.09.2030) Anlage C §C.1, §C.2, §C.5 (PDF S. 112–113: 8 m versetztDerived from the document
MJ OPTIMAMJModular, rosette0.73 m · 1.09 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.22-986 MJ OPTIMA (17.03.2021, Bescheide 13.06.2022, 17.04.2024, 06.07.2026, bis 23.07.2027) Anlage C S. 2 §C.5 (PDF S. 90: V-Halter nicht am RandDerived from the document
MJ UNI 70/100MJFrame1.5 m · 2 m · 2.5 m · 3 m0.74 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.1-184 MJ UNI 70 (21.06.2019, verl. 06.07.2026 bis 13.07.2027) Anlage B S. 3 §B.5 a–c (PDF S. 94), §B.9, Anlage C S. 1 (PDF S. 98: langer Anker am Innen- und Außenständer, V-Anker), S. 3 (PDF S. 100: Schutzwand 2 V-Anker im 5-Felder-Bild, strengste Lesung 2 je angefangene 5 Felder), S. 8 (PDF S. 105: Netz, Randrahmen alle 2 m, 2 V-Anker im 5-Felder-Bild, strengste Lesung 2 je angefangene 5 Felder), S. 12 (PDF S. 109: L = 3,0 m, 4 m-Ebene alle Rahmen)Derived from the document
MJ UNI TOP 65MJFrame1.5 m · 2 m · 2.5 m · 3 m0.65 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.1-902 MJ UNI TOP 65 (11.08.2026, 18.08.2026 – 18.08.2031) Anlage B S. 3–4 §B.5 a–c (PDF S. 197–198: V-Halter nicht am Rand), §B.9 (PDF S. 200), Anlage C S. 1 (PDF S. 204: 1 V-Halter je 5 Felder), S. 4 (Netz: 2 V-Halter im 5-Felder-Bild, strengste Lesung 2 je angefangene 5 Felder), S. 7 (Schutzwand: 2 V-Halter im 5-Felder-Bild, strengste Lesung 2 je angefangene 5 Felder)Derived from the document
MJ UNI-CONNECTMJFrame0.73 m · 1.09 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.1-872 MJ UNI-CONNECT 70 DUO (16.03.2022, Bescheid 10.06.2024) Anlage B S. 5 §B.5 a–c (PDF S. 403), Anlage C S. 1 (PDF S. 413: Fußnote 1 kurzer Gerüsthalter entfällt vor der geschlossenen Fassade, Rohr ø48,3 + NK innen unter den V-Haltern), S. 5/6 (PDF S. 417/418: Netz ohne Konsolen), S. 11 (Plane), S. 14 (PDF S. 426: Schutzwand, 2 V-Halter im 5-Felder-Bild, strengste Lesung 2 je angefangene 5 Felder)Derived from the document
Müller & Baum FIX 70SMüller & BaumFrame2 m · 2.5 m · 3 m0.74 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.1-182 Rahmengerüst FIX 70S (30.01.2020, verl. 21.01.2025 bis 31.01.2030) Anlage B S. 3 §B.5 a–c (PDF S. 135: Dreiecksanker nicht am Rand), Anlage C S. 1/2 (PDF S. 140/141: mindestens zwei Dreiecksanker pro 5 Felder, durchgehend bei H = 4,0 m), S. 8/11 (2 pro 5 Felder als 2 je angefangene 5 Felder gelesen, strengste Lesung)Derived from the document
OLAN (Facade)OLANFrame0.73 m · 1.09 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m2 m2 m / Every 2nd standard, staggered rowsOLAN Euro+ Instrukcja montażu wyd. 2 (05.2017) §4.F s. 20 (PDF 21) + §9 A schemat s. 44 (PDF 45): kotwy na każdym poziomie co drugi stojak, przesunięte o jeden stojak (każdy stojak co 4 m), kotwa podwójna V jedna na 5 pól i minimum dwie na każdej kotwionej kondygnacji, do 34 mFrom the document
OLAN (Modular)OLANModular, rosette0.73 m · 1.04 m · 1.09 m · 1.4 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m · 1.09 m2 m4 m / Every 2nd standard, staggered rowsOLAN «R+ modular scaffolding – Operation and Maintenance Manual» (Żabokliki 2020) ch. 9 s. 46–47, §4 s. 24, rule 22 s. 9Derived from the document
ÖZLER (Shoring/Falsework)ÖZLERShoring1 m · 1.2 m · 1.5 m · 2 m · 2.5 m1 m · 1.2 m · 1.5 m2 m≈4 m / Every 2nd standard, staggered rowsGeneral rule (no document)Estimate (≈): no manufacturer rule on file; follow the supplier's manual
PERALTA Donnergerüst 70 SPERALTAFrame0.73 m · 1.09 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.1-936 PERALTA – Donnergerüst 70 S (30.06.2023, geänd. 04.03.2026, bis 20.03.2031) Anlage B S. 4 §B.5 + Tab. B.2 (PDF S. 342–343), Anlage C S. 1 (PDF S. 354: Gerüsthalter "lang" oder Blitzanker), S. 21Derived from the document
PERI UPPERIModular, rosette0.75 m · 1 m · 1.25 m · 1.5 m · 1.75 m · 2 m · 2.25 m · 2.5 m · 3 m0.75 m · 1 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.22-863 (22.09.2025) Anlage C §C.1/§C.5 (mindestens zwei Gerüsthalter oder ein Dreiecksanker je AnkerlageDerived from the document
PERI UP EasyPERIFrame1.5 m · 2 m · 2.5 m · 3 m0.67 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.1-957 PERI UP Easy (16.05.2022, Bescheide 26.09.2022, 30.09.2024, 12.05.2025, b = 0,67 m, bis 16.05.2027) Anlage C S. 3–4 §C.5 (PDF S. 304–305), Anlage C S. 9 (PDF S. 310: mindestens zwei Gerüsthalter oder ein Dreiecksanker je Ankerlage), Anlage D S. 3 (PDF S. 322: Grundvariante 1a)Derived from the document
Pilosio MPPilosioModular, rosette0.83 m · 1.15 m · 2.5 m0.83 m · 1.15 m2 m≈4 m / Every 2nd standard, staggered rowsD.Lgs. 81/2008 art. 125 c. 6 «ancorato … ogni due piani di ponteggio e ad ogni due montanti, con disposizione di ancoraggi a rombo» (art. 138 c. 5), art. 133 c. 1 (oltre 20 m: progetto)Estimate (≈): rule not yet checked against the manufacturer's document; follow the supplier's manual
Plettac ConturPlettacModular, rosette0.75 m · 1 m · 1.25 m · 1.5 m · 2 m · 2.5 m · 3 m0.74 m · 1.06 m · 1.39 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.22-843 plettac contur (9.5.2019, forl. 19.3.2024 bis 3.4.2029) Anl. C §C.1, §C.5 s.1–2Derived from the document
Plettac PD 70/100PlettacFrame1.5 m · 2 m · 2.5 m · 3 m0.73 m2 m4 m / Every 2nd standard, staggered rowsplettac Distribution PD 70/100 Assembly and use manual (Ostrzeszów, July 2013, EN 12810-3N, certificate Z/002/034/25 valid 19.12.2025–18.12.2028) §1.1 pt 3/7/8 (PDF S. 5: max h 24 m), §3.1.3.6 (PDF S. 21), anchor drawings PDF S. 24–26 (● long anchors)Derived from the document
Plettac SL 70 AluPlettacFrame2.5 m · 3 m0.74 m2 m4 m / Every standardDIBt Z-8.1-29.1 plettac SL 70-Alu (16.12.2020, verl. bis 03.01.2031) Anlage B §B.1 (PDF S. 110), §B.5 (PDF S. 111), Anlage C (3,00 m, teilweise offen: 4 m durchgehend)From the document
Plettac SL 70/100PlettacFrame1.5 m · 2 m · 2.5 m · 3 m0.73 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.1-29 PLETTAC SL 70 (5.6.2020, endr. 29.10.2020, 28.5.2025 og 21.8.2026, bis 3.6.2030) Anl. B §B.1 (PDF S. 167), §B.5 a s.3–4, Tab. B.3 s.8, Anl. C s.6–8/17/18Derived from the document
Plettac Distribution (Modular)Plettac DistributionModular, rosette0.7 m · 1.1 m · 1.5 m · 2 m · 2.5 m · 3 m0.74 m · 0.97 m2 m4 m / Every standardPlettac Distribution «Instruction manual on assembly and use of PDM and PDM/c» (June 2025) §5.1 c (PDF S. 27: H = 24 m), §5.2.9 s. 28 (PDF p30), Fig. 30 (PDF S. 29: long anchors), §5.1 hFrom the document
Ponteggi Dalmine (Facade)Ponteggi DalmineFrame1.8 m · 2.5 m0.75 m · 1.05 m2 m4 m / Every 2nd standard, staggered rowsMarcegaglia Buildtech «Manuale di utilizzo – sistemi di ponteggio a telai prefabbricati» (07/2017) s. 32 «ogni 22 mq di ponteggio di facciata», s. 30 (> 20 m: progetto)Derived from the document
Ponteggi Dalmine (Modular)Ponteggi DalmineModular, rosette1.8 m · 2.5 m · 3 m0.81 m · 1.14 m2 m≈4 m / Every 2nd standard, staggered rowsD.Lgs. 81/2008 art. 125 c. 6 «ancorato … ogni due piani di ponteggio e ad ogni due montanti, con disposizione di ancoraggi a rombo» (art. 138 c. 5), art. 133 c. 1 (oltre 20 m: progetto)Estimate (≈): rule not yet checked against the manufacturer's document; follow the supplier's manual
RARIS Alu (Facade)RARISFrame2.5 m0.7 m2 m4 m / Every 2nd standard, staggered rowsRARIS «Schele de faţadă — Manual de utilizare» s. 13 (ancorare < 20 m: cadre laterale din 4 în 4 m, celelalte din 8 în 8 m în zig-zag)From the document
Ringer DoppelgeländerRingerFrame2.5 m0.65 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.1-858 Ringer Doppelgeländer (10.02.2020, verl. 11.02.2025 bis 14.02.2030) Anlage B §B.1 (PDF S. 51), §B.5 a–c, Anlage C S.1–S.7 (PDF S. 56–62)From the document
ROLLE BLIZZARD S-70ROLLEFrame0.73 m · 1.09 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.1-974 ROLLE BLIZZARD S-70 (06.02.2025, geänd. 01.04.2026, bis 28.03.2031) Anlage B S. 3–4 §B.5 + Tab. B.2 (PDF S. 264–265), Anlage C S. 1 (PDF S. 276: Gerüsthalter "lang" oder Blitzanker), S. 20Derived from the document
RUBO RK (klinowe)RUBOModular, wedge2.09 m · 2.53 m0.65 m · 0.95 m2 m≈4 m / Every 2nd standard, staggered rowsRozp. MI 6.02.2003 (Dz.U. 2003 nr 47 poz. 401) §115 ust. 1–3: siatkę kotew określa dokumentacja producenta lub projekt, ≥ 2,5 kN na kotwę, pomost ≤ 1,5 m nad najwyżej położoną linią kotewEstimate (≈): rule not yet checked against the manufacturer's document; follow the supplier's manual
Scaffolding Center SC 70Scaffolding CenterFrame1.5 m · 2 m · 2.5 m · 3 m0.74 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.1-990 SC 70 (03.03.2026, 16.03.2026 – 16.03.2031) Anlage B S. 3–4 §B.5 a–c (PDF S. 184–185), Anlage C S. 6 (PDF S. 194: 1 Dreieckhalter je 5-Felder-Abschnitt, ① Anker bei teilweise offener Fassade), S. 10 (PDF S. 198: Netz 2 Dreieckhalter je 5-Felder-Abschnitt in jeder Ankerebene, nur gezeichnet, strengste Lesung 2 je angefangene 5 Felder), S. 11 (PDF S. 199: Plane, strengste Lesung 2 je angefangene 5 Felder), S. 32 (PDF S. 220: Kopplungsrohr unter allen Durchstiegen)Derived from the document
Scaffolding Center SC 73Scaffolding CenterFrame0.73 m · 1.09 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.1-991 SC 73 (20.01.2022, bis 20.01.2027) Anlage B S. 4 §B.5 + Tab. B.2 (PDF S. 245–246), Anlage C S. 1 (PDF S. 256: Gerüsthalter "lang" oder Blitzanker)Derived from the document
FRAMESCAFF 73Scafom-RuxFrame0.73 m · 1.09 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.1-924 FRAMESCAFF 73 (05.07.2021, geänd. 02.09.2025, verl. 18.06.2026 bis 06.07.2031) Anlage B S. 3–4 §B.5 (PDF S. 255–256: «Unbekleidete Gerüste sind in Höhe 4 m durchgehend zu verankern»Derived from the document
Scafom-Rux RINGSCAFFScafom-RuxModular, rosette0.73 m · 1.04 m · 1.09 m · 1.4 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m · 1.09 m · 1.4 m2 m4 m / Every standardDIBt Z-8.22-869 RINGSCAFF (09.04.2021, geänd. 02.04.2025, verl. 20.03.2026 bis 11.04.2031) Anlage C S. 2 §C.5 (PDF S. 91: jeder Ständerzug alle 4 m, in der obersten Ebene jeder StänderzugDerived from the document
Scafom-Rux SUPERScafom-RuxFrame2 m · 2.5 m · 3 m1 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.1-185.2 RUX Super 100 (20.02.2023, bis 13.02.2028) Anlage B §B.5 a (PDF s. 131), Anlage C S.1 «8 m versetzt, Zusatzanker in H = 4 m», S.3 «Zusatzanker in H = 4 m, 20 m, 24 m»Derived from the document
Scafom-Rux SUPER 65Scafom-RuxFrame2 m · 2.5 m · 3 m0.65 m2 m4 m / Every standardDIBt Z-8.1-185.1 RUX SUPER 65 (30.06.2023, geänd. 23.01.2024, bis 05.01.2027) Anlage B §B.5 (PDF S. 153–154), Tab. B.3/B.4 (PDF S. 159–160), Anlage C S. 1 (PDF S. 163), S. 3 (PDF S. 165: Innen- und Außenkonsolen), S. 4 (PDF S. 166: Netz, 2 V-Halter im 5-Felder-Bild, strengste Lesung 2 je angefangene 5 Felder), S. 6 (PDF S. 168: Plane, jeder Knoten), S. 8 (PDF S. 170: Schutzwand, 2 V-Halter in der obersten Ankerlage)Derived from the document
SGB CUPLOKSGBCuplock1.25 m · 1.3 m · 1.8 m · 2.5 m · 3 m1.3 m2 m4 m / Every standardSGB CUPLOK® User Manual UK (Brand Energy & Infrastructure Services UK, 2016) s. 48 (PDF) «A. CUPLOK 2.0m lifts - 4m tie pattern · Horizontal spacing - every standard · Vertical spacing - maximum 4.0m», s. 36 Table 4 (8m tie pattern ≤ 4 lifts without foot ties), p31 rules 4 + 6, p32 «limit heights … to 12 lifts (24m)», p29 «unsheeted scaffolds only»Derived from the document
SIGMA (Facade)SIGMAFrame0.73 m · 1.09 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m2 m4 m / Every standardSIGMA 73LB DTR «Instrukcja montażu i użytkowania rusztowania SIGMA 73LB» §2.2.2 s. 12, §5.1, §5.3, §5.6, Rys. 21 s. 25From the document
SIGMA RTM (Wedge)SIGMAModular, rosette0.73 m · 1.04 m · 1.09 m · 1.4 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m · 1.09 m2 m4 m / Every 2nd standard, staggered rowsSIGMA RTM DTR «Instrukcja montażu i użytkowania rusztowania modułowego SIGMA RTM» 09/2024 §5.1, §5.3 s. 29 (PDF), Rys. 31 s. 32From the document
Solideq RAMSCAFFSolideqFrame0.73 m · 1.07 m · 1.57 m · 2.07 m · 2.57 m · 3.07 m0.73 m2 m4 m / Every standardSolideq RAMSCAFF, RISE sertifikat C900487 utg. 1 2022-10-01 (gyldig til 2032-10-01) s. 7 vilkår 6 + Monteringsanvisning Ramscaff 2022-02 (norsk) s. 33 §2.5.1, s. 34 fig. 4.3, s. 4 (maks. 24 m + 0,5 m)Derived from the document
StepUp CuplockStepUpCuplock0.91 m · 1.22 m · 1.52 m · 1.83 m · 2.13 m · 2.44 m · 3.05 m1.22 m · 1.52 m2 m≈4 m / Every 2nd standard, staggered rows29 CFR § 1926.451(c)(1)(ii): first tie at the 4:1 height, then ≤ 20 ft (≤ 3 ft wide) / ≤ 26 ft (7.9 m) vertically, at each end and ≤ 30 ft (9.1 m) along (the same numbers reprinted in WACO ORN1701 p. 20 F «Scaffolding Safety Guidelines»). StepUp publishes no tie rule (StepUp catalogs 2024-02)Estimate (≈): rule not yet checked against the manufacturer's document; follow the supplier's manual
StepUp Frame & BraceStepUpFrame1.22 m · 1.52 m · 1.83 m · 2.13 m · 2.44 m · 3.05 m0.91 m · 1.07 m · 1.52 m1.93 m≈4 m / ≤ 6 m apart29 CFR § 1926.451(c)(1)(ii): first tie at the 4:1 height, then ≤ 20 ft (≤ 3 ft wide) / ≤ 26 ft (7.9 m) vertically, at each end and ≤ 30 ft (9.1 m) along (the same numbers reprinted in WACO ORN1701 p. 20 F «Scaffolding Safety Guidelines»). StepUp publishes no tie rule (StepUp catalogs 2024-02)Estimate (≈): rule not yet checked against the manufacturer's document; follow the supplier's manual
StepUp RingLockStepUpModular, rosette0.91 m · 1.22 m · 1.52 m · 1.83 m · 2.13 m · 2.44 m · 3.05 m0.73 m · 1.09 m · 1.29 m2 m≈4 m / Every 2nd standard, staggered rows29 CFR § 1926.451(c)(1)(ii): first tie at the 4:1 height, then ≤ 20 ft (≤ 3 ft wide) / ≤ 26 ft (7.9 m) vertically, at each end and ≤ 30 ft (9.1 m) along (the same numbers reprinted in WACO ORN1701 p. 20 F «Scaffolding Safety Guidelines»). StepUp publishes no tie rule (StepUp catalogs 2024-02)Estimate (≈): rule not yet checked against the manufacturer's document; follow the supplier's manual
Tobler MATOToblerFrame2 m · 2.5 m · 3 m0.7 m2 m4 m / Every 2nd standard, staggered rowsDIBt Z-8.1-937 Tobler MATO 1 (15.08.2022 bis 15.08.2027, Bescheide 07.02.2023, 02.01.2024, 10.06.2024) Anlage B §B.1 (PDF S. 87), §B.5, Anlage C S.1, S.4–S.6Derived from the document
Tubesca-Comabi M368 (Modular)Tubesca-ComabiModular, wedge0.8 m · 1 m · 1.5 m · 2 m · 2.5 m · 3 m0.8 m · 1 m2 m4 m / Every 2nd standard, staggered rowsTubesca-Comabi «Notice de montage M368/R200P/R200R» 100-00035775-ind.2 (09.2024) §14.1 s. 68 (cas 1: extrémités tous les 4 m, autres files tous les 8 m en quinconce, 24 m², «immédiatement au-dessous du plancher (ou maximum à 0.15 m)»), s. 69 (protection couvreur: chaque file au dernier niveau de plancher), §6.1 s. 34 (> 24 m: étude BEAC)Derived from the document
Tubesca-Comabi R200 ProgressTubesca-ComabiFrame1.5 m · 2 m · 2.5 m · 3 m0.8 m2 m4 m / Every 2nd standard, staggered rowsTubesca-Comabi «Notice de montage M368/R200P/R200R» 100-00035775-ind.2 (09.2024), R200 PROGRESS: §14.1 s. 68 (cas 1: extrémités tous les 4 m, autres files tous les 8 m en quinconce, 24 m², «immédiatement au-dessous du plancher (ou maximum à 0.15 m)»), s. 69 (protection couvreur: chaque file au dernier niveau de plancher), ch. 5 s. 30 (NR 24 / 20 / 16 m², R 12 / 10 / 8 m² pour une maille de 3 / 2,5 / 2 m), §6.1 s. 34 (> 24 m: étude BEAC)Derived from the document
ULMA BRIOULMAModular, rosette0.7 m · 1.02 m · 1.5 m · 2 m · 2.5 m · 3 m0.7 m · 1.02 m2 m≈4 m / ≤ 6 m apart, staggered rowsULMA Guía de Usuario Andamio Multidireccional BRIO, dok. 02FAN08, s.66/s.82/s.156-157 (1 feste per 24 m²) (not published online)Estimate (≈): rule not yet checked against the manufacturer's document; follow the supplier's manual
Waco Frame (USA)WacoFrame1.52 m · 2.13 m · 3.05 m0.91 m · 1.52 m2.01 m4 m / ≤ 6 m apartWaco RED frame scaffolding brochure ORN1701 (BrandSafway 2020) p. 20 «Scaffolding Safety Guidelines» F (SSFI): first tie at 4 × the minimum base, vertical ≤ 26 ft (7.9 m), at each end and ≤ 30 ft (9.1 m) alongDerived from the document
WACO Narrow Frame (USA)WacoFrame1.52 m · 2.13 m · 2.44 m · 3.05 m0.7 m2.01 m4 m / ≤ 6 m apartWACO ORN1701 p. 5 (Narrow Frame 2'-3 5/8" × 6'-7")Derived from the document
WACO RED Access Frame (USA)WacoFrame1.52 m · 1.83 m · 2.13 m · 2.44 m · 3.05 m1.52 m2.01 m4 m / ≤ 6 m apartWaco RED frame scaffolding brochure ORN1701 (BrandSafway 2020) p. 20 «Scaffolding Safety Guidelines» F (SSFI): first tie at 4 × the minimum base, vertical ≤ 26 ft (7.9 m), at each end and ≤ 30 ft (9.1 m) alongDerived from the document
WACO RED Box Frame (USA)WacoFrame1.22 m · 1.52 m · 1.83 m · 2.13 m · 2.44 m · 3.05 m0.91 m · 1.52 m1.55 m4 m / ≤ 6 m apartWaco RED frame scaffolding brochure ORN1701 (BrandSafway 2020) p. 20 «Scaffolding Safety Guidelines» F (SSFI): first tie at 4 × the minimum base, vertical ≤ 26 ft (7.9 m), at each end and ≤ 30 ft (9.1 m) alongDerived from the document
Yagmur Iskele (H-Type)YagmurFrame2 m · 2.5 m · 3 m0.75 m · 1.05 m2 m4 m / Every standardYağmur «Güvenlikli İskele Sistemi Mamul El Kitabı» (2026-07) §9.1.9 s. 43 (ankraj: tüm panolar, 6 m kaplamasız, 4 m fileli, 2 m brandalı), s. 9 (24 m üzeri hesap)Derived from the document
Yagmur Iskele (Ringlock)YagmurModular, rosette0.75 m · 1.5 m · 2 m · 2.5 m · 3 m0.75 m · 1.05 m2 m4 m / Every standardYağmur «Flanşlı İskele Sistemi Mamul El Kitabı» (2026-07) §11 s. 66–68 (ankraj: 6 m kaplamasız, 4 m fileli, 2 m brandalı, 24 m), s. 9 (24 m üzeri hesap)Derived from the document
Cup-lock JGJ 166 (China)Several makers (system type)Cuplock1.2 m · 1.5 m0.9 m · 1.2 m1.8 m≈3.6 m / ≤ 4.5 m apartJGJ 166-2016 表6.2.1 (PDF s. 45–46: 二步三跨, 步距 1.8 m, 横距 0.9 / 1.2 m, 纵距 1.5 / 1.2 m, H 34–50 m by w0), §6.2.9-2 (PDF s. 48: «水平投影间距不得超过三跨,竖向垂直间距不得超过三步,… 悬臂高度不得超过两步»), §6.2.9-3 (PDF s. 49: 转角处、开口型端部, ≤ 层高且 ≤ 4m), §6.2.9-4, -7 (PDF s. 49: «从底层第一道水平杆处开始设置», «距架体碗扣主节点距离不应大于 300mm») (not published online)Estimate (≈): rule not yet checked against the manufacturer's document; follow the supplier's manual
CuplockSeveral makers (system type)Cuplock1.25 m · 1.3 m · 1.8 m · 2.5 m · 3 m1.3 m2 m≈4 m / Every standardGeneral rule (no document)Estimate (≈): no manufacturer rule on file; follow the supplier's manual
Japanese frame scaffold (枠組足場)Several makers (system type)Frame0.91 m · 1.22 m · 1.52 m · 1.83 m0.61 m · 0.91 m · 1.22 m1.7 m9 m / ≤ 8 m apart労働安全衛生規則 §570 第1項第5号イ (枠組足場: 垂直方向 9 m、水平方向 8 m 以下)Derived from the document
Japanese wedge scaffold A-type (くさび緊結式足場)Several makers (system type)Modular, wedge0.9 m · 1.2 m · 1.5 m · 1.8 m0.6 m · 0.9 m · 1.2 m1.8 m≈5 m / ≤ 5.5 m apart労働安全衛生規則 §570 第1項第5号イ (単管足場: 垂直方向 5 m、水平方向 5.5 m 以下)Estimate (≈): rule not yet checked against the manufacturer's document; follow the supplier's manual
Japanese wedge scaffold B-type (くさび緊結式足場)Several makers (system type)Modular, wedge0.9 m · 1.2 m · 1.5 m · 1.8 m0.6 m · 0.9 m · 1.2 m1.9 m≈5 m / ≤ 5.5 m apart労働安全衛生規則 §570 第1項第5号イ (単管足場: 垂直方向 5 m、水平方向 5.5 m 以下)Estimate (≈): rule not yet checked against the manufacturer's document; follow the supplier's manual
Korean system scaffold (시스템비계)Several makers (system type)Modular, rosette0.91 m · 1.22 m · 1.52 m · 1.83 m0.61 m · 0.91 m · 1.22 m1.9 m≈5 m / ≤ 5 m apart산업안전보건기준에 관한 규칙 제69조 제5호 (벽 연결재: 제조사가 정한 기준)Estimate (≈): rule not yet checked against the manufacturer's document; follow the supplier's manual
KwikstageSeveral makers (system type)Modular, wedge0.76 m · 0.81 m · 1.27 m · 1.83 m · 2.44 m · 3.05 m0.76 m · 1.27 m2 m4 m / Every 2nd standard, staggered rowsWaco Kwikform «Guidelines for safe use of scaffold – Wedgelok / Kwikstage» PPM51 (08/2013) s. 5 «Scaffold Ties» 1(a)/(b) + table «Tie configurations for scaffolds up to 30 metres» (each end + ≤ every 3rd standard, first ≤ 4.0 m, ≤ 4.0 m upDerived from the document
Rusztowanie warszawskieSeveral makers (system type)Frame1.58 m1.58 m1.73 m≈1.73 m / Every 2nd standard, staggered rowsRozp. MI 6.02.2003 (Dz.U. 2003 nr 47 poz. 401) §115 ust. 1–3: siatkę kotew określa dokumentacja producenta lub projekt, ≥ 2,5 kN na kotwę, pomost ≤ 1,5 m nad najwyżej położoną linią kotewEstimate (≈): rule not yet checked against the manufacturer's document; follow the supplier's manual
Shoring / falseworkSeveral makers (system type)Shoring1 m · 1.5 m · 2 m · 2.5 m1.3 m2 m≈4 m / Every 2nd standard, staggered rowsGeneral rule (no document)Estimate (≈): no manufacturer rule on file; follow the supplier's manual
Tube & couplerSeveral makers (system type)Tube and coupler1 m · 1.2 m · 1.5 m · 2 m · 2.4 m0.73 m · 1.09 m · 1.4 m2 m≈4 m / ≤ 6 m apartGeneral rule (no document)Estimate (≈): no manufacturer rule on file; follow the supplier's manual
Tube & coupler JGJ 130 (China)Several makers (system type)Tube and coupler1.2 m · 1.5 m1.05 m · 1.3 m1.8 m≈3.6 m / ≤ 4.5 m apartJGJ 130-2011 表6.1.1-1 (s. 27, PDF s. 36: 二步三跨, lb 1.05 / 1.30 m, h 1.80 m, H 32 / 30 m, w0 = 0.4 kN/m²), 表6.4.2 (PDF s. 41: 竖向 ≤ 3h, 水平 ≤ 3la, ≤ 40 m²), §6.4.3 (PDF s. 41–42: «偏离主节点的距离不应大于 300mm», «从底层第一步纵向水平杆处开始设置»), §6.4.4 (PDF s. 42: 开口型两端, ≤ 层高且 ≤ 4m)Estimate (≈): rule not yet checked against the manufacturer's document; follow the supplier's manual
ЛРСП-40Several makers (system type)Frame2 m · 2.5 m · 3 m0.98 m2 m2 m / Every 2nd standard, staggered rowsЛРСП-40 паспорт (ТУ 5225-001-11713507-04) §4.5 с. 6 «через 4м в шахматном порядке», с. 8 «Схема крепления лесов к стене» (каждый ярус с 4 м, стойки через одну, в шахматном порядке), §2.1 «Максимальная высота лесов, м 40» (not published online)Derived from the document
ЛСК-60Several makers (system type)Modular, rosette1 m · 1.2 m · 1.5 m · 2 m · 2.5 m · 3 m1 m · 1.2 m2 m≈4 m / Every 2nd standard, staggered rowsПриказ Минтруда России № 782н (ред. 29.04.2025) п. 89 (крайние стойки через ярус, верхний ярус через два пролета, 1 крепление на 50 м²)Estimate (≈): rule not yet checked against the manufacturer's document; follow the supplier's manual

How to read the table

  • Bay length: the distance between two standards along the facade, as the catalogue gives it for every length variant of the system.
  • Depth: the width of the scaffold from the wall side to the outside, one value per depth the system comes in.
  • Lift: the main lift height the app erects the system in (its own frame height where it has one), so decks lie about one lift apart. Scaffold bay length chart has the same bays and depths in feet and inches.
  • Ties, vertical: the largest distance between two tie rows. Along the face: which standards in a tie row are tied (every one, every second in staggered rows, or a largest spacing).
  • Tie rule source: the first document the rule cites, as the catalogue records it, in its own language. The CSV holds the full source with every document and page.
  • Status: «From the document» is checked against the cited document; «Derived from the document» is the engine's reading of it where the document leaves a choice; «Estimate (≈)» is not yet checked.

Limits

  • The number of wall ties follows the system's tie rule. Their positions must be checked against the manufacturer's assembly instructions.
  • Round corners, silos and hanging scaffolds are in Pro. A round scaffold is not a standard configuration and needs a calculation or the supplier's documentation. A hanging scaffold (Layher Allround and HAKI Universal) always needs a structural calculation from the supplier or an engineer.

Cite as

ScaFix, «Scaffold system specifications (ScaFix catalogue)», version 28b091ff9e2f, 2026-11-20, https://scafix.app/scaffold-system-specs

Questions and answers

What is the most common scaffold bay length?

In ScaFix's catalogue, 2.5 m: 48 of the 115 systems offer it, followed by 3 m (41) and 2 m (38). Bays run from 0.7 m to 3.07 m, and most systems offer several. The most offered depth is 0.73 m, in 44 systems.

What lift height do scaffold systems use?

ScaFix erects 98 of the 115 systems in 2 m lifts; the others use 1.8 m (3), 2.01 m (3), 1.9 m (2), 1.93 m (2), 1.52 m (1), 1.55 m (1), 1.7 m (1), 1.73 m (1), 1.98 m (1), 2.04 m (1) and 2.13 m (1), their own frame heights.

The decks lie on those lifts, so the lift height sets the working levels.

Where do the wall-tie rules come from?

89 rules come from the manufacturer's own manual or approval, 12 from a regulation and 6 from a third party's document; 8 systems use ScaFix's general rule. 91 of the 115 rules are checked against their document; the others show «≈» estimates. The tie spacing page lists each rule with its document and page.

Can I download the scaffold system specifications?

Yes, as CSV (https://scafix.app/data/scaffold-system-specs.csv) and JSON (https://scafix.app/data/scaffold-system-specs.json), in English, one row per system with every bay length and depth, the lift height and the tie rule with its source and page references. The files need no account and hold the same 115 rows as the table on this page.

Sources

ScaFix plans each scaffold system from the documents that system's page names (the manufacturer's manual or approval, where one is on file); the rules come from EN 12811-1 and the national authority. Read 10 November 2026. The documents, not this page, decide how the scaffold is built: ScaFix plans, it does not approve.